For the operating room:
+ Temperature: 22 ° C 2oC
+ Relative humidity: t = <70%
+ purity level: Class ISO 7
+ Rotate air: 30-40 times / h.
+ 70% gas rotation recovery, 30% additional fresh air. Emission mode outside 100%
+ For clean corridors and postoperative areas:
+ Temperature: 24 ° C 2oC
+ Relative humidity: φt = <70%
+ level of cleanliness: ISO Class 8
+ Rotation no: 6-15 times / h
+ 70% gas reincarnation, 30% additional fresh air. Emission mode the outside for 100%
+ Differences between regions apply: Class ISO 7> ISO Class 8 = 7-12 Pa.
+ Level and clean area requirements:
Inside the operating room is designed to grade ISO 7 (walls and ceilings using panels, Vinyl wallpaper using antistatic and automatic doors)
+ corridor at level ISO 8 clean (use vinyl wallpaper, ceiling panels, wall epoxy)
Air Purification Equipment:
+ Using the most modern ventilation is now using gas dungthong oriented (Larminar flow)