1. ALL ELECTRICAL, DISTRIBUTION BOXES and switches WILL BE LOCATED at a height of 1.2 M-WALL (FROM the floor). ALL Sockets WILL BE PLACED at a height of 0.3 M WALL (FROM the floor). The DISTANCE FROM THEM to the EDGE of the DOOR is at LEAST 200 mm. The LAMP is MOUNTED on the CEILING. 2. ALL the TUBES THREADED POWER CABLE WILL BE INSTALLED in the WALL or the FLOOR, HAS a RADIUS of CURVATURE NOT LESS THAN 500 mm for EASY PULL CABLES LATER. THE LOCATION OF THE CONNECTION WILL USE CO, T OR SOFT RUBBER FITTINGS.3. ALL ELECTRICAL CABLES MUST BE COLOURED for the PHASE R (red), S (blue), T (yellow), N (white), EARTH (GREEN YELLOW STRIPES).4. The EQUIPMENT in CABINETS MUST BE LABELED UNDER the NAME RECORDED in the design.5. The SAFETY GROUND CONNECTION RESISTANCE of ELECTRICAL & EQUIPMENT MUST < 4 Ω (ACCORDING to the STANDARD). CONNECT THE SAFETY GROUND SHALL BE CONNECTED TO THE GROUNDING SYSTEM OF THE OVERALL SAFETY OF THE PLANT.