Factory Archetype Vietnam Medochemie
-A- Revision Date: April 01, 2015 Specifications - 0711 Package chiller - scroll and screw - Page 1/9
PACKAGE CHILLER 0711 - SCROLL AND SCREW
TABLE OF CONTENTS
1 GENERAL 2
1.1 SUMMARY 2
1.2 REFERENCES 2
1.3 2
1.4 submittals 2
1.5 closeout submittals .............................................. .................................................. . 2
1.6 Quality Assurance 2
1.7 Qualifications 3
PRE-INSTALLATION 1.8 Meetings ............................................ ............................................. 3
1.9 DELIVERY, STORAGE , AND HANDLING ............................................... ............................... 3
1.10 3
1:11 MAINTENANCE 3
2 3
............................................. 2.1 PACKAGED WATER Chillers .............................................. 3
2.2 GENERAL 3
.............................................. 2.3 Centrifugal Compressors ........................................... 4
2.4 MOTOR 4
2.5 Evaporator 4
2.6 CONDENSERS FOR WATER AND HEAT RECOVERY-cooled chillers .................................... 5
2.7 Refrigerant CIRCUIT ................................................. .................................................. 5
2.8 casing 5
2.9 CONTROLS 5
2:10 CHILLER NOISE AIR cooled Controlled ........................................... ......................... 7
2:11 CHILLER 7
Characteristics AND ELECTRICAL COMPONENTS ............................................ 2:12 ............ 7
SOURCE QUALITY CONTROL AND Tests 2:13 ............................... .......................................... 7
3 Execution 8
3.1 8
3.2 FIELD QUALITY CONTROL ............................................. .................................................. . 9
3.3 MANUFACTURER'S FIELD SERVICES ............................................ ...................................... 9
3.4 Demonstration AND TRAINING ....... .................................................. ............................ 9
4 SCHEDULE 9
4.1 REFER TO Drawings 9
Medochemie Factory Archetype Vietnam
-A- Revision Date: April 01, 2015 Specifications - 0711 Package chiller - scroll and screw - Page 2/9
1 GENERAL
1.1 SUMMARY
a) Section includes chiller package, charge of refrigerant and oil, controls and
control connections , chilled water connections, water connections condenser,
refrigerant connections, auxiliary water connections, starters.
b) Related Sections:
1. All the relevant mechanical and electrical sections
1.2 REFERENCES
a) Air-Conditioning and Refrigeration Institute:
1. ARI 550/590 - Water Chilling Packages Using the Vapor Compression
Cycle.
b) American Society of Heating, Refrigerating and Air-Conditioning Engineers:
1. ASHRAE 90.1 - Energy Standard for Buildings Except Low-Rise Residential
Buildings.
1.3 DEFINITIONS
a) Coefficient of Performance (COP) - cooling: The ratio of the rate of heat removal
to the rate of energy input, in Consistent units, for a complete refrigerating
system or some specific portion of mà under designated operating system
conditionsEND_SPAN.
b) Integrated Part-Load Value (IPLV): A single-number figure of merit based on
part-load EER, COP, or kW / ton Expressing part-load Efficiency for airconditioning and heat pump equipment on the basis of weighted operation at
Various load capacities for the equipment. IPLV 3.1 Shall not be lower coal as
per ARI 550/590.
1.4 submittals
a) Shop Drawings: Indicate components, assembly, dimensions, weights and loads,
required clearances, and location and size of field connections. Indicate valves,
strainers, and thermostatic valves required for complete system.
b) Product Data: Submit rated capacities, weights, specialties and accessories,
electrical requirements, wiring diagrams, and control diagrams.
c) Manufacturer's Installation Instructions: Submit assembly, support details,
connection requirements, and include startup instructions.
d) Manufacturer's Certificate and contractor compliance sheet: Certify products
meet or Exceed requirements rõ gồm những furnished but not
Produced by manufacturer.
e) Manufacturer's test results as indicated by the Latest version of ARI 550/590
method of testing Shall be submitted.
f) Manufacturer's Field Reports: Submit start-up report for each unit. Indicate
results of refrigerant leak test and pressure test.
1.5 closeout submittals
a) Operation and Maintenance Data: Submit start-up instructions, maintenance
data, parts lists, controls, and accessories. Include trouble-shooting guide.
1.6 Quality Assurance
a) Conform to ARI 550/590 code for testing and rating of reciprocating, scroll or
screw air cooled water chillers.
b) Performance Ratings: Coefficient of Performance (COP) and Integrated Part-Load
Value IPLV not less coal Prescribed by ASHRAE 90.1.
c) Perform Work in accordance with local codes and standard.
Medochemie Factory Archetype Vietnam
-A- Revision Date: April 01, 2015 Specifications - 0711 Package chiller - scroll and screw - Page 3/9
d ) Maintain one copy of each document on site.
1.7 Qualifications
a) Manufacturer: Company specializing in manufacturing products rõ in this
section with minimum ten years documented experience with service and
facilities.
b) Installer: Company specializing in Performing Work of this section with minimum
ten years documented experience.
1.8 PRE-INSTALLATION Meetings
a) convene minimum one week prior to commencing work of this section.
1.9 DELIVERY, STORAGE, AND HANDLING
a) Accept chillers on site in factory packaging. Inspect for damage.
b) Protect from weather indoor chillers by storing under roof.
1:10 WARRANTY
a) Furnish two year manufacturer warranty for complete coverage to include
materials and Labor gồm assembly or as the period Mentioned in the
condition of contract mà larger
MAINTENANCE 1:11 SERVICE
a) Furnish service and maintenance of chiller for two years from the Date of Substantial
Completion.
b) Examine monthly unit components. Clean, adjust, and lubricate equipment.
c) Include systematic Examination, adjustment, and lubrication of the unit, and
controls and adjustments checkout. Repair or replace parts in accordance with
manufacturer's operating and maintenance data. Use Produced by parts
of original equipment manufacturer.
d) Perform work units from service without Removing the during normal building
hours Occupied.
e) Provide emergency call back service at all hours for this maintenance period.
f) Maintain locally, near Place of the Work, adequate stock of parts for replacement
or emergency Purposes. Have personnel available to Ensure Fulfillment of this
maintenance service, without unreasonable loss of time.
g) Perform maintenance work using competent and qualified personnel under
supervision of original manufacturer or installer.
h) Do not assign or transfer to an agent or subcontractor maintenance service without
prior Written consent of the Owner
2 PRODUCTS
2.1 PACKAGED WATER Chillers
a) Product Description: Factory Tested and assembled, packaged, water cooled,
liquid chillers, semi-hermetic screw consisting of compressors, compressor motors,
condensers, evaporator, refrigeration accessories, instrument and control panel
gồm gages and indicating lights, auxiliary components and accessories, and
motor starters.
2.2 GENERAL
a) The design, construction, materials and finishes of all units Shall Be Suitable for
outdoor use in the locations, climatic and operating conditionsEND_SPAN indicated in this
specification and drawings. The units shall is khởi be on site by the
Manufacturer's qualified technical staff.
b) The units shall is be with the individual multi circuit (minimum 2 circuits) packaged and
fully factory assembled, Tested, internally wired ful