Not have a self test of FIRE FIGHTING; Not yet have written maintenance FIRE PROTECTION system at the plant. II/reality check -Fire water supply system: the company has equipped 2 fire pumps (pump electric motor 01 Q = 10 l/s, H = 50; n 01 m.c. Diezel pump with the same parameters), the water in the throat, out of the House. Through testing, some throat box hydrants outside were damaged. -Automatic fire alarm systems: 2 fire cabinets in the room; The fire alarm, smoke heat; The combination of bells, lights, fire alarm push button. Through testing, 1 Central Cabinet no active, 1 central cabinet failed. The current system is faulty.-Fire approach: the company who built the PACC under model PC11 circular 66/2014/TT-BCA practical organization and fire projects in July 2015.-Fire extinguishing media: Through check out the vehicles were equipped with long but not routine maintenance led to many comments were broken, takes effect. -Goods, raw material, arranged neatly. -There are more building the garage Shack but does not yet have a safe FIRE PROTECTION solutions. At the end of the mobile car Shack borders Takagi factory hampered, affecting roads for fire trucks, FIRE FIGHTING and safety distances.