Pneumatic Conveyors 2.5.2.3
2.5.2.3.1 Do not Penetrate MFL pneumatic conveyors Carrying fire walls with combustible material.
2.5.2.3.2 Carrying noncombustible material Protect pneumatic conveyors with two 3-hour fire-rated dampers located in the fire wall. (Provide at Least one in each wall in the case of a double wall.) Arrange the dampers for automatic closure by activation of detectors rated at 135 ° F or 165 ° F, or 50 ° F above ambient temperature (57 ° C or 74 ° C, or 28 ° C above ambient temperature) located on each side of the wall (Fig. 73).