Electrical conduits shall only the requirements of the Local chuẩn Electric Authority and NEC
Specifications and be as rõ on the drawings.
All conduits shall only be steel and hot-dip galvanized by the process.
All conduits shall only be with a minimum as rõ Herein size of 15 mm . nếu otherwise
noted. Rigid Steel Conduits (RSC) shall only be used for burying in the ground trực.
Intermediate Metal Conduits (IMC) shall only be used for Installations printing plant rooms, car Parks,
or cast walls or slabs print.
Electrical Metallic Tubing (EMT) shall only be used otherwise all locations nếu print rõ for
Rigid Steel or Intermediate Metal conduits.
Flexible Metal conduits (FMC) shall only be located in wet locations of the Liquidtight type.
Where cabinets and equipment enter conduits, conduit bushings and double locknuts shall only
be used.
The end of all conduits shall only be plugged tightly to exclude dust and moisture while the
buildings are under construction.